4 Core 50mm2 Copper XLPE Insulation Power Cable

1, Application electrical cable

The product is to used as power distribution system of electricity at rated voltage 0.6/1KV1.8/3KV3.6/6KV

6/10KV8.7/15KV12/20KV21/35KV26/35KV.

 

 

2, Product Features electrical cable

(1)The cable wire core allows long time working temperature of 90°.
(2)When core is in short-circuir(max 5s) the temperature should not exceed 250°.
(3)While installation the ambient temperature should not be lower than 0°C, and the bending radius should not be less than 20-time.

 

 

3, Parameter electrical cable

Rated Voltage U0/U(KV)

0.6/1

1.8/3

3.6/6

6/10

8.7/15

12/20

21/35

26/35

Partial discharge test(PC)

 

 

≤10

≤10

Industrial frequency 5min pressure resistance 

test (KV)

3.5

6.5

12.5

21

30.5

42

73.5

91

4h industrial frequency test

 

 

14.4

24

35

48

84

104

Inquiry